Six Danfoss AK-SM800A Flaws Threaten Remote Control
Danfoss AK-SM800A flaws could allow a remote attacker to take over a refrigeration controller without logging in, Dutch security consultancy Midnight Blue said earlier this week. The six vulnerabilities remain unpatched, and the newest firmware, version 5.4.0, does not fix them, according to the researchers.
The AK-SM800A controls store fridges and freezers and can be managed remotely by maintenance companies. Government cybersecurity agencies in Belgium, Ireland and Germany have told operators to remove the controllers' management interfaces from the public internet. The Belgian and Irish agencies say that updating firmware, changing default passwords or enabling Strict mode is not sufficient on its own for a controller that remains exposed.
Strict mode is a login protection feature that requires encrypted connections and session tokens. However, one of the six flaws is located in the gateway that enforces Strict mode. The Centre for Cybersecurity Belgium says internet exposure must be removed even when the firmware is current and Strict mode is enabled.
The warnings follow attacks against refrigeration controllers in France that began on October 11, followed by a second wave across Europe that started last week. The attacks caused unwanted defrost cycles and destroyed stock. Germany's federal IT security agency, the BSI, says the AK-SM800A was also involved in earlier incidents in which refrigeration units in several countries were tampered with. The BSI has no information that the six newly reported flaws were exploited, and neither the other agencies nor Midnight Blue has linked these vulnerabilities to those earlier incidents.
Midnight Blue examined firmware version 5.3.2, which was then the newest release, and says every version up to and including 5.3.2 is affected. The consultancy found the flaws during less than an hour of manual review using firmware available for download from the vendor. Technical details are being kept private while disclosure work continues with Danfoss, the Danish manufacturer. No CVE identifiers have been assigned.
Five flaws affect web request handlers that do not require a login. They sit inside a program running as root, meaning the highest level of control on the device. Midnight Blue ran code as root through one of those flaws on older firmware version 3.3.0 and found the same bugs in version 5.3.2.
Strict mode blocks almost all of the web attack surface available to users who have not logged in, including the flaw used in that demonstration. The sixth flaw affects the separate gateway that blocks every request except login until authentication is complete. In an emulator running firmware 5.3.2 with Strict mode enabled, the researchers caused that gateway to crash. They say the crash could be turned into code execution with additional work, and that the gateway lacks basic exploit protections such as stack canaries, which help detect certain memory attacks.
Code running as root could let an attacker change controller settings, start defrost cycles and hide those actions from the logs. The researchers also found that the controllers do not use secure boot, a startup check that helps prevent unauthorised software from loading. They say an attacker could therefore install code that survives a factory reset and a firmware update, or make a controller unusable until it is replaced. Midnight Blue believes the code almost certainly contains more flaws and argues that fixing vulnerabilities one at a time, or relying on Strict mode alone, would use scarce security and personnel resources poorly.
Danfoss lists software package 5.4.0, dated November, as the newest AK-SM800A release. Its readme and November update guide describe upgrade steps, and the guide introduces a stricter password rule. Neither document mentions a vulnerability fix. In a follow-up statement carried by trade publication Cooling Post, Midnight Blue said the firmware was likely built on October 29 according to its file timestamp, before the second wave of attacks and well before the vulnerability reports, so it was not realistically able to include the fixes.
The BSI initially stated in a press release that version 5.4.0 was not affected. Later the same day, it corrected that statement and said it could not currently rule out that the version is affected. Danfoss's advisory page listed no advisory for the six flaws and no fix date had been published. Danfoss told Cooling Post on October 12 that most units affected in France were either older models no longer receiving updates or current AK-SM800A units running outdated firmware.
Operators should identify every controller whose management interface can be reached from the internet, including through a 4G or 5G modem, and remove that exposure. Remote access should be provided only through a secure VPN, which is a protected private connection, or a protected internal network. Restricting access through a firewall to a service company's IP addresses is only a short-term measure.
Operators should also check temperature setpoints, defrost schedules, alarm settings, user accounts and remote-access settings for changes they did not make. Anyone who suspects a compromise should change all credentials and verify that equipment connected to the controller is working properly. Before cutting off data sent to a refrigeration service company, operators should review contract and insurance terms and arrange protected remote access so monitoring can continue.
Danfoss's own update guide says the AK-SM800A should not be directly reachable from the public internet, and says that recommendation applies to every software version, including those with Strict mode enabled. Ireland's National Cyber Security Centre also recommends using the latest supported firmware, changing default passwords and enabling Strict mode, while warning that these steps must not be relied on alone. Danfoss fixed earlier AK-SM800A flaws in 2023 and 2025, including login bypass and command injection bugs, but the examined version 5.3.2 is newer than all of those fixes.
For organisations securing connected equipment and infrastructure, AEU-I provides security-first IT, infrastructure and consulting. The immediate lesson from this incident is to remove public exposure and establish protected remote access rather than wait for a firmware fix.